NEN 3140+A1:2015 en Norm
5.102.15
The replacement leakage current may be measured instead of the actual leakage current, but this shall always be supplemented with a measurement of the insulation resistance.The values from tables 102 and 103 apply to the replacement leakage current. NOTE The replacement leakage current is the current that flows away through the protective conductor or through foreign conducting parts when
NEN 3140+A1:2015 en Norm
5.102.17
It shall be established through measuring that the response current and time of earth leakage circuit breakers do not exceed the values assigned. The proper operation of the test button may only be checked after the measurements.
NEN 3140+A1:2015 en Norm
6.1.1   Induction
[not applicable]
NEN 3140+A1:2015 en Norm
6.2.4   Earthing and short-circuiting
6.2.4.1   General If it is not certain that all parts of the electrical installation which are to be worked on are dead, these parts shall be earthed and short-circuited. NOTE It is not always certain that an installation remains dead if: — the installation is not clearly arranged; — outside power supplies are possible; — a conductor can be electrically influenced.
NEN 3140+A1:2015 en Norm
6.2.7   Re-energizing after work
After the work has been completed and inspected, persons no longer required shall be notified that work is completed, no more work is permitted and they shall be withdrawn. All tools, equipment and devices used during the work shall be removed. When the nominated person in control of the work activity is satisfied that the electrical installation is ready to be re-energized, notification shall
NEN 3140+A1:2015 en Norm
6.3.0.102
Work activities in the live working zone may only be carried out by nominated persons or by persons who work under the uninterrupted supervision of at least a skilled person.
NEN 3140+A1:2015 en Norm
6.3.0.106
Live working may only be done after a separate and immediately preceding written order from the nominated person in control of a work activity.
NEN 3140+A1:2015 en Norm
6.3.0.107
Live working is only allowed if the risk of fire and explosion has been ruled out.
NEN 3140+A1:2015 en Norm
6.3.2.101
Instructions shall be given for: — keeping the tools, equipment and devices, and personal protective equipment in good condition; — checking these tools, equipment and devices, and personal protective equipment before use. 6.3.2 (continuation) On successful completion of the training a certificate of training shall be given to the participant to confirm that the personnel are
NEN 3140+A1:2015 en Norm
6.3.5   Working conditions
According to the complexity of the work, the working conditions shall define the rules to be followed in accordance with 6.3.1. The working conditions may include one or more of the following items: — description of the relationship between personnel involved in live working, such as the nominated person in control of the electrical installation and the nominated person in control of the
Zoeken in de websiteFilter resultaten
52 resultaten
Pagina
Nieuwe NEN 3140 sterk doorontwikkeld
Als trainer en adviseur NEN 3140, werk ik nu alweer een paar weken met de nieuwe NEN 3140 + A2 (December 2018). Deze nieuwe NEN 3140 is sterk doorontwikkeld. Veel zaken waar je in de praktijk vaak tegen aanloopt, zijn nu scherper en concreter geformuleerd. Ook zijn technische, organisatorische en maatschappelijke ontwikkelingen meegenomen in deze nieuwe uitgave. Dat begint al bij de installatieverantwoordelijke
Pagina
Veiligheid mag geen sluitpost zijn
Juridisch adviseur geeft uitleg over het belang van NEN 3140 Veiligheid is van groot belang bij elektrotechnische installaties. De norm NEN 3140 beoogt deze veiligheid voldoende te waarborgen. Toch is er in de praktijk nog wat te winnen, stelt mr. Klaas van der Kolk van juridisch advies- en trainingsbureau Nova Juridica. “Uiteindelijk gaat het erom dat iedereen aan het eind van de dag weer veilig