NEN 3140+A1:2015 en Norm
5.3.3   Inspection
5.3.3.1   The purpose of inspection is to verify that an electrical installation is in accordance with safety regulations and the specified technical requirements of the relevant standards; the inspection may include verification of the normal state of that installation. New electrical installations as well as modifications and extensions of existing installations shall be inspected prior to
NEN 3140+A1:2015 en Norm
5.3.3.3
Inspections shall be carried out with reference to relevant electrical drawings and specifications. 5.3.3.3.101   In special cases, the person responsible for an electrical installation may decide that the inspections can be carried out without drawings and specifications, for example in simple and clearly arranged installations.
NEN 3140+A1:2015 en Norm
5.3.3.5.102
Inspections shall be carried out using suitable tools, equipment and devices and protective equipment that prevent hazards, duly considering the hazards of uninsulated live parts.
NEN 3140+A1:2015 en Norm
5.101.6.1
When visually inspecting an installation it is checked whether: a) the necessary drawings are present and the correct information is indicated; b) the different (installation) parts are clearly identifiable; c) any damage present does not cause a hazard; d) the electrical equipment at least corresponds to the installation requirements; e) the gangways intended for
NEN 3140+A1:2015 en Norm
5.101.6.2
When inspecting an installation by measuring and testing, it shall be checked that the requirements have been met as regards: a) the protective conductors and their connections; b) the circuit impedances of the electrical system; c) the earth distribution resistance of earth electrodes; d) the insulation resistance of each section of the installation; e) the safe
NEN 3140+A1:2015 en Norm
5.101.6.3
The following criteria shall apply to measurement and testing according to 5.101.6.2: a) The uninterrupted state of the protective conductors and their connections shall be measured with: 1) a measurement of the phase-earth circuit impedance or 2) a measurement of all the separate protective conductors with a measurement current greater than or equal to 0.2 A. b)
NEN 3140+A1:2015 en Norm
5.101.6.5
The earth distribution resistance of earth electrodes shall be measured using an alternating voltage. NOTE If the measurement is not reliable in urban areas, measuring the circuit impedances will suffice.
NEN 3140+A1:2015 en Norm
5.101.6.8
It shall be established through measuring that the response current and time of earth leakage circuit breakers do not exceed the values assigned. The proper operation of the test button may only be checked after the measurements.
NEN 3140+A1:2015 en Norm
5.102.1   General
The electrical installations of extensive, complex and sizeable work equipment shall be inspected according to 5.101. Safety functions, such as emergency shutdown switches and collision protection devices of such extensive, complex and sizeable work equipment shall be checked at least once a year.
NEN 3140+A1:2015 en Norm
5.102.2
Electrical work equipment shall be inspected with suitable regularity.The time between two successive inspections depends on: a) the frequency of use; b) the expertise of the user; c) the environment; d) the risk of damage. NOTE The purpose of regular inspections is to detect any defects that have occurred during use and that pose a hazard.
Zoeken in de websiteFilter resultaten
52 resultaten
Pagina
Nieuwe NEN 3140 sterk doorontwikkeld
Als trainer en adviseur NEN 3140, werk ik nu alweer een paar weken met de nieuwe NEN 3140 + A2 (December 2018). Deze nieuwe NEN 3140 is sterk doorontwikkeld. Veel zaken waar je in de praktijk vaak tegen aanloopt, zijn nu scherper en concreter geformuleerd. Ook zijn technische, organisatorische en maatschappelijke ontwikkelingen meegenomen in deze nieuwe uitgave. Dat begint al bij de installatieverantwoordelijke
Pagina
Veiligheid mag geen sluitpost zijn
Juridisch adviseur geeft uitleg over het belang van NEN 3140 Veiligheid is van groot belang bij elektrotechnische installaties. De norm NEN 3140 beoogt deze veiligheid voldoende te waarborgen. Toch is er in de praktijk nog wat te winnen, stelt mr. Klaas van der Kolk van juridisch advies- en trainingsbureau Nova Juridica. “Uiteindelijk gaat het erom dat iedereen aan het eind van de dag weer veilig